animal incinerators

The incinerator shall be equipped with a Diesel oil tank that will be supplied with DO from our DO tank located in the

power station. The tank shall be equipped with level switches and appropriate solenoid valves for automatic filling of

the tank. The tank shall also be equipped with a magnetic level indicator, level switches and appropriate drain valves,

separate overflow and vent pipes.

Oil-fired multi-stage waste incinerator of pyrolytic type shall be installed complete with interconnecting flue gas

ductwork between the incinerator and the chimney outlet.

 

The unit shall be manufactured in accordance with the latest ASME code, BS and DIN standards.

 

The waste disposal shall be environmentally acceptable and the incineration emission shall comply with the admissible

emission limits (international EC-Standards). The visibility of flue gases shall not exceed one Ringelmann. The waste

shall be completely burnt and the content of un burnt organic matter of the ash shall not exceed 3%.

 

The unit shall allow for a minimum of 2.0 seconds retention time.

 

1.2        QUALITY ASSURANCE:

 

  1. Coordinate the entire assembly of incinerator, stack, controls, fuel supply.

 

  1. Provide written certification that the entire assembly has been coordinated to achieve the required performance

and to provide the required features.

 

  1. Equipment, installation, and operation shall conform to NFPA 82. Where conflicts exist between NFPA 82 and this

specification, this specification shall govern.

 

1.3        SUBMITTALS:

 

  1. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

 

  1. Incinerator:

 

  1. Arrangement, description of construction, and outline drawings of incinerator and accessories showing

clearances and dimensions.

 

  1. Predicted performance including burn time based on waste composition specified.

 

  1. Calculation of secondary chamber retention time.

Waste Incineration Therapy Style TS75( PLC).


Average 50-100 kg/hour Burn Rate

Items/Model

TS75( PLC)

Principle

Waste Incineration Therapy

Burn Cost

Average 50-100 kg/hour

Feed Ability

Ordinary 200-300 kg/feeding

Control Mode

PLC( Programmable Reasoning Controller Burner)

Face Oil Paint

800 ℃

Combustion Chamber

768 Liters (0.768 M3)

Inner Measurements

1200x800x800mm

Added Chamber

384 Liters (0.384 M3)

Smoke Filter Chamber

Yes

Feed Setting

Manual

Voltage

210/240V 50Hz 1P

Power

1.3 Kw

Oil Intake (kg/hour)

Typical 20.4( D.O)

Thermal ability( kw/hour)

166-332

Gas Consumption (m3/hour)

***

Temperature Level Degree Monitor

Digital Show

Oil Tank

3000L

Feed Door

60x50cm

Smokeshaft

10Meter

Chimney Kind

Stainless-steel

1st. Chamber Temperature

800 ℃–– – – -1000 ℃

2nd. Chamber Temperature Level Degree

1000 ℃ -1200 ℃

Residency Time

2.0 Sec.

Gross Weight

7500kg

Outside Dimensions

260x160x250cm( without smokeshaft)

We offer singular burning chamber, dual combustion chambers, 3 burning chambers and multi-combustion

chambers waste incinerators for lab, center, clinical facility, clinical facility, hygiene specialist waste devastation with scientific

non reusable, organic waste, clinical plastic waste, contaminated materials, red bag waste, needle disposal, gauze and additionally plasters,

secured sharp containers, pathological waste, trace-chemotherapeutic wastes, and so forth.

Our collection of incinerators provide for little to big range family pet cremation relevant business, such as fowl ranches, livestock

ranches, lamb ranches, pig ranches, stables, kennels, screening laboratory, catteries, pet dog crematoriums. Vendor clear up rate for incinerator consumer,

The incinerator burn waste in primary combustion chamber and burn the smoke from primary combustion chamber again to 

make sure environmentally friendly with no black smoke, smelless, reduce pathogenic bacteria infection.

System solutions for medical waste environmental, including waste incineration, smoke emission treatment, high-temperature 

sterilization, ultraviolet sterilization lamp, waste shredder, needle destroyer, medical waste package, sharp containers, etc.

The pet cremation equipment humanized design with movable platform, small space covers for modern pet cremation 

business owner all over the world.

The containerized mobile incinerator mounted in ISO container before leave factory, pre-installation, no incineration house 

build construction, movable by truck and ultraviolet lamp sterilization inside.

We are growing brand for environmental protection field, and market share with most of 

Africa, Middle East, Southeast Asia countries and part of North America, Europe territory. We are trusted partner for governmental 

organizations, non-profit organizations, international contractors, logistics organizations, military, pet cremation business owners, etc. 

We have export experience more than 40 countries, including war zone like Iraq, Afghanistan, Somalia, South Sudan.

supply clinical burner, medical center burner, family pet burners, hog burners, pet dog cremation tools, small incinerator,

pet dog burner, pet dog burner, mobile burner, little pet dog burner, transmittable waste pyrolysis tool, lab

heater.

burner.


250kgs per human resources capacity waste incinerator


Burner Design TS250 PLC, Review

This design is small waste incineration tools for little waste result. Construction

is dual/double combustion chamber with 02 units oil burner, batch load incineration equipment. 
Waste feed chamber is 1800Liters (1.8m3, TS250 PLC). Primary & Secondary combustion chambers
and smoke filter chamber. Batch load on the bottom of chamber. Incinerator PLC panel control suit for local operation. 

Key Product Listing per 01 collection

Key Burning Chamber

Extra Combustion Chamber

Smoke Filter Chamber

Incinerator PLC Control Circumstances

Smokeshaft:10.0 Meters

*( upgrade to Stainless-steel, complimentary cost)

Italy oil/gas heater: 02 systems

Oil Container (if oil fuel): 300Liters








Items/Model

TS200( PLC)

Image

Principle

Solid Waste Incineration Therapy

Melt Price

Average 250 kg/hour

Feed Ability

Requirement 350kg/feeding

Control Establishing

PLC( Programmable Logic Controller Burner)

Burning Chamber

1800L

Internal Measurements

150x110x110cm

Second Chamber

750L

Smoke Filter Chamber

Yes

Feed Mode

Handbook

Voltage

220V

Power

0.9 Kw

Oil Intake (kg/hour)

Common 28

Gas Usage (m3/hour)

Typical 33.6

Temperature Level Display

Digital Existing

Temperature Level Degree Security

Yes

Oil Tank

300L

Feed Door

80x60cm

Smokeshaft

10Meter

Smokeshaft Kind

Stainless-steel

1st. Chamber Temperature Level

800 ℃–– – – -1000 ℃

2nd. Chamber Temperature Level

1000 ℃ -1200 ℃

Residency Time

2.0 Sec.

Gross Weight

8500kg

Exterior Dimensions

300x160x190cm

Heater procedure should certainly be Automatic On/Off

Gas: diesel

The supplier need to supply needed details for the very best of the installment

This burner with “PYROLYTIC” burning need to have:

;

・ Refractory concrete:

§. Thickness: ≥ 100 mm

§. Nature: 42% of Al203

・ Guard in coarse panels:

§. Thickness: ≥ 75 mm

・ Nature: Calcium silicate.

* Heater of illumination of waste, with gas, typical mono-bloc casting directing diving flame, lights and additionally safety and security of digital ignition, permanent air circulation, electro-magnetic sluice entry of guideline in addition to isolating valve.

* Plate of burning in Carborundum, staying clear of the taking care of glass along with slags.

A chamber of short article burning of gases

* A heating system of burning of gases,

* A gadget of shot of air making it possible for a total recombustion of gases,

* A device of air inlet of air conditioning of waste gases,

* A sheath of clearing of the gases charred.

* Carcass in solid sheet steel with assistance of web link.

* Structure of the refractory;

・ Refractory concrete:

§ Thickness: ≥ 150 mm

§ Nature: 65% of Al203

・ Protect in rugged panel:

§ Thickness: ≥ 85 mm

Nature: Calcium




burner manufacturer 200kgs/h


Waste is thermally rotted in the main chamber at temperature degrees of 800 ° C +. The resulting aeriform products are entirely oxidized in the second chamber at higher temperature levels with ample resident time. Various other specs are as adheres to. A burning chamber of waste:

* Flawlessly limited door for the hands-on loading of waste. The filling should certainly be Handbook, Set Tons

* A heater of lights which the use is restricted to the ignition of waste.

* Frontage of packing with door seals risen on hinges, wheel of screw plug, versatile joint, in addition to packing securing out of refractory.

* The insulation of the burning chamber need to be comprised of refractory blocks, having a high internet material of light weight aluminum as well as guards blocks in order to assure a minimum temperature level on the outside sheet steel.

* Composition of the refractory

Burning Capability

Max. 200kgs/h

Supporting Gas

Diesel

Kind of Heating Unit

Monoblock automatic heating units

Temperatures

Key Chamber: 800 ° C ± 50 ° C. Extra Chamber: 1300 ° C ±

50 ° C. Kind.

240 W.

Pump pressure.

* Make-up of the refractory

Burning Capacity

Max. 200kgs/h

Sustaining Gas

Diesel

Kind of Heating System

Monoblock automated heating systems

Temperatures

Main Chamber: 800 ° C ± 50 ° C. Extra Chamber: 1300 ° C ±

50 ° C. Kind.

Refractory thickness.

240 W.

Pump stress.

Refractory thickness.

115 mm thick.

Product.

Refractory blocks.

Insulation density.

50 mm thick.

Type.

Centrifugal.

Inflection.

Manual damper control.

Product of Construction.

Mild Steel.

Sort of temperature controller.

Digital.

End up & & paint kind.

Dual coat.

Material of construction & & capacity

. Mild Steel/ Plastic, appropriate capacity.

Other Standard Accessories.

Diesel oil degree sign, piping with shutoffs & & Non-return shutoff.

Aesthetic Monitoring of Gas.

Offered.

No. of Burners.

2 one in primary and also in second chamber).

Type & & Design

. Monoblock automated oil fired.

Make.

Riello.

Fuel.

Diesel.

Fuel shipment.

10 C 20 kg/h.

Discharging phase.

1.

Thermal power.

118 C 236 kW.

Motor power.

240 W.

Pump pressure.

10 C 12 bar (basic calibration), Max. pressure 15 bar.

Electrical supply.

Single phase 220V, 50Hz.

Material of building and construction.

Burned bricks.

Height.

9 meters from ground degree.


pet incinerator prices

Spare part list –After burners

Item description                                                No of required

Motor     2

Control box  2

Pump couplings   4

Photo cells    2

Sets ht. leads       2

Sets electrodes    4

Oil valve       1

Nozzle   2

 

Spare part list –Ram loader

Item description                                                No of required

Reed switch          4

Seal kit  1

 

Medical waste incinerator Accessories

-Clean out tools

-Loading and ash removal methods.

-Fuel storage tank with the two pump and all accessories.

-Flue gas cleaning system

-Stack discharge.

Medical waste incinerator civil work

-Construct incinerator foundation

-Provide stack support

-Provide open steel structure room for the incinerator.

Medical waste incinerator submittal shall include:-

-Detail installation drawing

-Incinerator and auxiliary product data

-Test reports

-Certificates like CE, ISO,LR, FNOR, TUV and UL

-Energy analysis report

-Project experience

-Pollution control equipment emission rate.

-Noise level limitation.

-Quality assurance

-guarantee

Containerized Mobile Kind Tool Device Waste Burner


Medium Unit – to handle an average waste production of 500 kg/day.Minimum load capacity: 600 kg.Maximum load capacity: 1,000 kg.Nominal burning rate: 55-80 kg/hr (= 440 C 640kg range per 8hour day).

Items/Model

TS50( PLC)

Image

Idea

Waste Incineration Therapy

Melt Price

Criterion 50-100 kg/hour

Feed Capability

Average 200-300 kg/feeding

Control Mode

PLC( Programmable Reasoning Controller Burner)

Optional Upgrade Containerized Mobile Kind Burner

ISO 20′ ′ ′ ′ Complete Container

Burning Chamber

560L

Interior Measurements

1000x800x700mm

2nd Chamber

280L

Smoke Filter Chamber

Yes

Feed Setting

Manual

Voltage

210/240V 50Hz 1P

Power

1.3 Kw

Oil Consumption (kg/hour)

Ordinary 20.4( D.O)

Thermal ability( kw/hour)

166-332

Gas Intake (m3/hour)

***

Temperature Degree Screen

Digital Present

Oil Container

1000L

Feed Door

60x50cm

Smokeshaft

10Meter

Smokeshaft Kind

Stainless-steel

1st. Chamber Temperature Level Degree

800 ℃–– – – -1000 ℃

second. Chamber Temperature Level

1000 ℃ -1200 ℃

Residency Time

2.0 Sec.

Gross Weight

7500kg

Outside Measurements

260x160x250cm( without smokeshaft)



medical incinerators

* medical incinerators, The insulation of the combustion chamber should be composed of refractory bricks, having a
high content of aluminium and insulates bricks in order to assure a minimum temperature on
the outside sheet metal.
* Composition of the refractory;

?    Refractory concrete :
?    . Thickness    : ≥100 mm
?    . Nature: 42% of Al203
?    Insulate in fibrous panels :
?    . Thickness: ≥75 mm
?    Nature: Calcium silicate.
* Burner of lighting of waste, with fuel, standard mono-bloc casting guiding  plunging flame, lighting and safety of electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.
* Plate of combustion in Carborundum, avoiding the fixing of glass and slags.

18.    A chamber of post combustion of gases
* A burner of combustion of gases,
* A device of injection of air allowing a total recombustion of gases,
* A device of air inlet of cooling of waste gases,
* A sheath of evacuation of the gases burnt.
* Carcass in strong sheet steel with support of connection.
* Composition of the refractory;
?    Refractory concrete :
?    Thickness    : ≥150 mm
?    Nature: 65% of Al203
?    Insulate in fibrous panel :
?    Thickness: ≥85 mm
?     Nature: Calcium

Dual Chamber Incinerator available for sale 50-200kgs per hr( in supply).


We supply Double Chamber Incinerator with primary chamber size average 1570Liters and burnning rate 50kgs per hour,100kgs per hour,150kgs per hour,200kgs per hour.

the incinerators are now ready for shipping.

Contact with us for quick respond: +86-13813931455

Secret Product Listing per 01 collection

Trick Burning Chamber

Secondly Burning Chamber

Smoke Filter Chamber

Incinerator PLC Control Situation

Smokeshaft:10.0 Meters

*( upgrade to Stainless-steel, cost-free price)

Italy oil/gas burner: 02 devices

Oil Container (if oil gas): 300Liters

Items/Model

TS150( PLC)

Idea

Waste Incineration Therapy

Shed Rate

Criterion 50/100/150/ 200 kg/hour

Feed Capability

Average 750kg/feeding

Control Establishing

PLC( Programmable Thinking Controller Incinerator)

Combustion Chamber

1570L

Internal Dimensions

150x100x105cm

Second Chamber

750L

Smoke Filter Chamber

Yes

Feed Setting

Manual

Voltage

210/230V 50/60Hz

Power

0.9 Kw

Oil Usage (kg/hour)

Ordinary 20.4( D.O)

Thermal ability( kw/hour)

166-332

Gas Use (m3/hour)

***

Temperature Level Show

Digital Existing

Temperature Protection

Yes

Oil Storage Tank

300L

Feed Door

80x60cm

Smokeshaft

10Meter

Smokeshaft Kind

Stainless-steel

1st. Chamber Temperature Level

800 ℃–– – – -1000 ℃

secondly. Chamber Temperature Level

1000 ℃ -1200 ℃

Residency Time

2.0 Sec.

Gross Weight

8500kg

Exterior Dimensions

300x160x280cm( without smokeshaft)


Simply just how you can find practical incinerators for your regional site?


The heater with dual/double combustion chamber as well as completely dry filter chamber, two gas burner from

Italy created, hot sale version for little range waste result, the ability is 30kgs per hr

as well as likewise 50kgs per human resources.

Heater is not a cost-effective gadgets, generally the tiny range version’s cost around $5,000 usd per device

We are famous small scale incinerator manufacturer and brand, dispatch incinerator products 
and best services with lower price for customer all around the world.

as well as massive range version’s price even more than $50,000 usd each. Before purchase one system burner,

you have to make clear adhering to products:

A, burn what?

you have to make clear adhering to products:

A, burn what? Incinerator is a incineration tools, function is fire waste. What kind of

waste you want to treatment?

B, tiny or huge? This according to the waste result each day or the waste volume per

feed time, like animal dimension.

C, fuel? Incinerator use oil or gas fuel, usually, gas fuel is cheaper than oil and the smoke

cleaner than oil gas version. Some neighborhood website do not have gas supply system.

As well as other technology items, like power( 220v, 380v), waste feed door kind, burner framework, etc.

WWW.HICLOVER.COMWaste Incinerators Auto Roll Air Filters
Nanjing Clover Medical Technology Co.,Ltd.

Tel: +86 -25 -8461 0201

Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC) TS100(PLC)
Burn Rate (Average) 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour 100 kg/hour
Feed Capacity(Average) 20kg 40kg 60kg 100kg 200 kg
Control Mode PLC PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L 1200L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm 120x100x100cm
Secondary Chamber 50L 110L 180L 280L 600L
Smoke Filter Chamber Yes Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual Manual
Voltage 220V 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24 14–28
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1 10–32.2
Temperature Monitor Yes Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L 200L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm 80x60cm
Chimney 3Meter 3Meter 5Meter 5Meter 10Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800–1000 800–1000 800–1000 800–1000 800–1000
2nd. Chamber Temperature 1000-1200 1000-1200 1000-1200 1000-1200 1000-1200
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg 6000kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm 260x150x180cm


Waste burners extra components


HICLOVER now supplies additional components including:

— — — — Burners (diesel oil, LPG or gas)

— — — — Facet for heaters

— — — — Fire ropes

— — Incinerator chamber maintenance items

— — — — Air Follower